Sometimes it is desirable to change the reported position of the motor without it physically moving, effectively changing the origin of the axis. This can be achieved through EPICS by applying an offset to the reported motor position and by setting the position in steps in the motor. TO do this:
- See if you can home the axis instead of setting the value directly
- Ensure the motor IOC is running
- Put the instrument in to manager mode if it is not already in the mode
- Menu bar: IBEX -> Manager mode
- Go into the
Motorsperspective in the client - Bring up the OPI for the desired motor by double clicking the relevant square in the table
- Click on
More details... - In the
Calibrationsection,- ensure that it says Frozen above the offset box
- switch
Calfromusetoset 
- Either
- Change the
Offfield to apply an offset to the current position - Change the current position directly by changing the
MoveAbsUserfield in theDrivesection
- Change the
-
Don't forget to switch the
Calfield back toUseonce you're done or the motor won't move.
- Finally leave manager mode