Introduction

The main PLC on RIKEN is responsible for controlling and monitoring the various systems on the beamlines, e.g. vacuum equipment and magnet cooling. The Schneider PLC IOC runs a CMD file specific to RIKEN which then loads a specific DB file to give access to designated PLC registers (memory addresses) via the ASyn MODBUS driver.

The groups of variables are as follows: (all are readonly, apart from the vacuum valve controls, see below)

  • Separator vacuum status
  • Solenoid status
  • Kickers water, vacuum and MOL (Magnet Off Light) status
  • Kickers status and output (voltage and current)
  • GH (Gauge Head) vacuum gauge status
  • LV (Line Valve), AMGV (All Metal Gate Valve) and FSOV (Fast Shut Off Valve) vacuum valve status
  • LV, AMGV, FSOV, control (writable ````from IBEX, but only to open the valves)
  • BP (Backing Pump) and TP (Turbo Pump) vacuum pump status
  • PIV (Pump Isolation Valve) interlock status
  • LV, AMGV, FSOV, BPV1 interlock status
  • BB (BeamBlocker) status and information
  • Magnets Klixon interlock status (a Klixon is a thermal switch which opens/closes at a set temperature)
  • Magnets cooling water flow status, rate and temperature
  • RBox (Rectifier Box) and bypass interlock status
  • MOL (Magnet Off Light) status (purely the status of the bulb, not the magnet state)

The PLC IOC also loads a separate DB file (TEMPMON) for monitoring temperatures of a selection of magnets (RQ1, RQ2, RB1) and is purely for logging purposes. This is at the request of the Electrical Controls Group who are performing an experimental analysis.

Connection and Configuration

The PLC is connected to the controls network using a fixed/static IP address which is specified in the globals.txt file. Also in this file are macros to specify the connection type (TCP in this case) and which configuration (CMD file) to load.