Introduction

The main PLC on RIKEN is responsible for controlling and monitoring the various systems on the beamlines, e.g. vacuum and magnet cooling. The Schneider PLC IOC loads a DB file specific to RIKEN which then gives access to designated PLC registers (memory addresses) via the ASyn MODBUS driver. The groups of variables are as follows: (all are readonly, apart from the vacuum valve controls)

  • Separator vacuum status
  • Solenoid status
  • Kickers water, vacuum and MOL (Magnet Off Light) status
  • Kickers status and output (voltage and current)
  • GH (Gauge Head) vacuum gauge status
  • LV (Line Valve), AMGV (All Metal Gate Valve) and FSOV (Fast Shut Off Valve) vacuum valve status
  • LV, AMGV, FSOV, control (writable from IBEX)
  • BP (Backing Pump) and TP (Turbo Pump) vacuum pump status
  • PIV (Pump Isolation Valve) interlock status
  • LV, AMGV, FSOV, BPV1 interlock status
  • BB (BeamBlocker) status and information
  • Magnets Klixon interlock status (a Klixon is a thermal switch which opens/closes at a set temperature)
  • Magnets cooling water flow status, rate and temperature
  • RBox (Rectifier Box) and bypass interlock status
  • MOL (Magnet Off Light) status (purely the status of the bulb, not the magnet)

The PLC IOC also loads a separate DB file (TEMPMON) for monitoring temperatures of a selection of magnets (RQ1, RQ2, RB1) and is purely for logging purposes. This is at the request of the Electrical Controls Group who are performing an experimental analysis.