Notifications
You must be signed in to change notification settings - Fork 2
Eurotherm
John Holt edited this page Sep 24, 2019
·
25 revisions
Wiki > The Backend System > Specific Device IOC > Temperature Controllers > Eurotherm
The eurotherm is one of the most common temperature controllers at ISIS. Most beamlines have at least one eurotherm if not more.
Eurotherms can be calibrated by selecting a calibration file in the OPI (None.txt for uncalibrated). By default this looks at a common calibrations repository, but can be set to a instrument-specific local one via IOC macro. See Calibration Files for more info.
- If the protocol timeouts are increased too much the IOC will go into alarm states as some scans depend on the timeout. Do not increase the timeout beyond the tested value in the protocol file!
- The eurotherm protocol uses variable terminators.
There are many different models of eurotherm so they may have different connections.
General:
- Connection: Serial 9 Pin
- Null terminator?: Unknown
- Gender?: Unknown
HRPD:
- Port: serial cable needs to be pluged into the RH 9 pin port labelled "J" not the 25 pin one labelled "H"